So wählen Sie einen Transformator für ein Batterie-Energiespeichersystem aus

So wählen Sie einen Transformator für ein Batterie-Energiespeichersystem aus: Dimensionierung von Trockentransformatoren für BESS, Spannungsanpassung und Kompatibilität mit dem Leistungsumrichter (PCS)

A Battery Energy Storage System (BESS) requires more than batteries, a Battery Management System (BMS) and a Power Conversion System (PCS). The transformer is also a critical part of the electrical system, connecting the battery storage equipment to the facility electrical network or utility grid.

Selecting the right BESS transformer requires consideration of transformer capacity, voltage, frequency, phase, cooling, insulation, installation environment and the operating characteristics of the energy storage system. A properly selected transformer can improve system reliability, support stable power conversion and provide the required voltage matching between the PCS and the electrical grid.

What Does a Transformer Do in a BESS?

A transformer in a battery energy storage system is mainly used for voltage conversion and electrical isolation.

The PCS typically operates on a low-voltage AC side while the grid or facility distribution system may operate at a higher voltage. The transformer connects these two voltage levels and allows power to flow between the energy storage system and the electrical network during charging and discharging.

A typical BESS power structure may look like:

Battery → BMS → PCS → Transformer → Grid or AC Load

During charging, AC power from the grid is converted by the PCS and stored in the battery. During discharge, the battery supplies DC power to the PCS, which converts it back to AC before the transformer raises or matches the voltage for the grid or facility.

For this reason, the transformer must be selected according to the electrical characteristics of the PCS and the complete BESS application rather than only the battery capacity.

1. Determine the Required Transformer Capacity

The first step is to determine the required transformer kVA rating.

A common starting point is to calculate the maximum AC power handled by the PCS and then consider power factor, efficiency, load profile and future expansion.

For three-phase systems:

kVA = √3 × Voltage × Current / 1000

If the BESS PCS has a rated active power of 1000kW and operates close to unity power factor, the transformer capacity will generally need to be around 1000kVA or higher, depending on the actual system design.

However, selecting exactly the same kVA rating as the PCS is not always appropriate. Engineers should consider:

  • PCS maximum continuous power
  • Charging and discharging requirements
  • Power factor
  • Transformer efficiency
  • Ambient temperature
  • Harmonic currents
  • Continuous operating conditions
  • Future system expansion

For industrial and commercial BESS projects, a suitable safety margin may also be considered to prevent continuous operation at the transformer’s maximum rated capacity.

2. Match the Transformer Voltage to the PCS and Grid

Voltage matching is one of the most important factors in BESS transformer selection.

For example, a system may use a PCS with a low-voltage AC output such as 400V, 415V, 480V or 690V, while the facility or utility connection requires a medium-voltage output.

The transformer may therefore perform a step-up function such as:

400V → 10kV

or:

480V → 13.8kV

The actual voltage combination depends on the PCS, local electrical network and project requirements.

The transformer manufacturer should receive the exact primary voltage, secondary voltage, phase configuration and frequency before preparing the final design.

For international BESS projects, frequency is also important. Systems may require 50 Hz oder 60 Hz, and the transformer must be designed accordingly.

3. Consider Dry Type vs Oil-Immersed Transformers

Both dry type and oil-immersed transformers can be used in energy storage applications, depending on the installation and project requirements.

Dry type transformers are often attractive for commercial and industrial BESS installations because they do not use liquid insulation and can be installed indoors or in equipment areas where fire and maintenance considerations are important.

Typical applications include:

  • Commercial BESS
  • Industrial energy storage
  • Solar + storage systems
  • Microgrids
  • Data centers
  • Factory energy management systems
  • Renewable energy projects

For larger outdoor utility-scale projects, oil-immersed transformers may also be considered because of their high capacity and cooling characteristics.

The choice should be based on capacity, installation location, fire protection requirements, environmental conditions, maintenance strategy and project specifications.

4. Pay Attention to PCS Harmonics

A BESS transformer does not always operate with a simple linear load.

Die Power Conversion System (PCS) uses power electronics to convert DC power from the battery into AC power. This switching process can introduce harmonic currents into the electrical system.

Therefore, transformer selection should consider the harmonic characteristics of the PCS.

Depending on the application, the project may require:

  • Low-loss transformer design
  • Increased thermal capacity
  • Appropriate winding configuration
  • Harmonic-resistant design
  • Suitable impedance
  • Additional power quality equipment

The actual requirements should be confirmed from the PCS manufacturer’s technical documentation.

For larger systems, harmonic analysis and load calculations should be completed before final transformer sizing.

5. Select the Correct Transformer Impedance

Transformer impedance affects voltage regulation and short-circuit current.

For BESS applications, the transformer impedance should be coordinated with the PCS, switchgear and grid connection requirements.

A transformer with inappropriate impedance can affect system voltage characteristics and fault-current levels.

Typical transformer specifications may include an impedance value such as 4%, 5%, 6% or a customized value, but the correct value depends on the complete electrical system.

Therefore, impedance should not be selected independently from the PCS and protection system.

6. Consider the Installation Environment

BESS installations may be located inside factories, commercial buildings, outdoor containers, solar farms or dedicated energy storage stations.

Environmental conditions can significantly affect transformer selection.

Important factors include:

  • Ambient temperature
  • Humidity
  • Dust
  • Salt exposure
  • Altitude
  • Indoor or outdoor installation
  • Ventilation
  • Enclosure protection
  • Cooling requirements

For outdoor BESS projects, the transformer may require a weather-resistant enclosure and appropriate protection against environmental exposure.

For indoor installations, ventilation and heat dissipation should be considered to maintain reliable operation.

Read More:Rectifier Transformer: Working Principle, Types, Applications and Selection Guide

7. Transformer Configuration for Solar + BESS Systems

Solar photovoltaic systems are increasingly combined with battery energy storage.

A typical solar + BESS electrical architecture may include:

PV Panels → Solar Inverter → AC Bus → Transformer → Grid

and:

Battery → PCS → AC Bus → Transformer → Grid

In some projects, the same transformer infrastructure may support both solar generation and battery storage, while other projects use separate transformers for different power conversion systems.

The appropriate configuration depends on the system capacity, grid connection voltage, operating strategy and electrical protection design.

For commercial and industrial projects, a custom dry type transformer can be designed according to the actual PV inverter, PCS and facility distribution requirements.

Choosing a BESS Transformer Manufacturer

When purchasing an energy storage transformer, buyers should provide the manufacturer with a complete technical specification rather than only the battery capacity.

Important information includes:

  • Transformer capacity in kVA
  • Primary voltage
  • Secondary voltage
  • 50 Hz oder 60 Hz Frequenz
  • Single-phase or three-phase
  • Transformer type
  • Cooling method
  • Insulation class
  • Impedance
  • Vector group
  • Installation location
  • Indoor or outdoor requirement
  • Environmental conditions
  • PCS model and power rating

Voltnex Power is a China-based industrial transformer manufacturer and factory providing customized dry type transformers and electrical power solutions for BESS, solar PV, industrial automation and renewable energy applications.

Transformer capacity, voltage, frequency, winding configuration, insulation, enclosure and other specifications can be customized according to project requirements. Voltnex Power supports OEM/ODM manufacturing, factory-direct supply and wholesale orders for international energy storage and renewable energy projects.

Final Thoughts

Selecting a transformer for a Battery Energy Storage System should be treated as part of the complete electrical system design. The correct transformer must match the PCS power rating, voltage, frequency, impedance, harmonic characteristics and installation environment.

For most projects, the key selection factors are kVA capacity, voltage matching, transformer type, PCS compatibility, cooling, environmental protection and future expansion requirements.

For BESS and solar energy projects requiring customized transformer specifications, Voltnex Power provides dry type energy storage transformers, Industrietransformatoren and custom OEM/ODM transformer solutions for commercial, industrial and renewable energy applications.

Need a BESS transformer for your project? Contact Voltnex Power for a custom transformer specification and engineering quotation.